Technical characteristics > MINI CAM SWITCHES Characteristics Data > Thermal current Ith 10 A > Rated operating current Ie - in AC 21 10 A - in AC 15 2.5 A > Motor performance in AC-3 - 3 x 230 V - 3 x 400 V 1.8 kW 2.2 kW > Motor performance in AC-23 - 1 x 230 V - 1 x 400 V 0.75 kW 1.1 kW - 3 x 230 V - 3 x 400 V 1.8 kW 3 kW > Rated insulation voltage Ui(V) 500 V > Rated operating current in DC-1 L/R < 1ms - 24 V DC - 40 V DC - 60 V DC - 110 V DC - 220 V DC 10 A 6A 2.5 A 0.7 A 0.3 A > Rated conditional short-circuit current 3 kA > Max. fuse rating 10 A > Degree of protection IP 65 IP 2x at the rear of the panel 2 x 1.5 mm2 max. 1 x 0.5 mm2 min. > Wire size (flexible and rigid) > Operating temperature - 20°C to + 50°C > Standards IEC 60947-1 IEC 60947-3 CSA 22.2 UL 508 > CAM SWITCHES Characteristics > For thermal current Ith Ic(A) PR 12 PR 17 PR 21 PR 26 PR 40 20 25 32 40 63 16 20 25 32 8 10 12 PR 63 PR 125 PR 160 63 200 250 50 63 160 200 - - - - > Rated operating current for AC-21 A Ie(A) (IEC 60 947-3) Switching of resistive loads including moderate overloads > Rated operating current for AC-15 A Ie(A) at 230V AC (IEC 60 947-3) Control of electromagnetic loads 6 213